Your advantages at a glance
Functional description
Operation
- Simple, intuitive menu-driven operation via a membrane keypad
- Process-oriented programming
- Language switching in the menu
- Individual configuration options for system manufacturers
Technology
- Convenient process visualization thanks to high-resolution colour displays
- Fast response times for control and image formation thanks to powerful processor
- Network-compatible via 2.5 GbE Ethernet
- Profibus (slave/master) connection possible with DE-CP XX2-01
- Profinet (slave/master) connection possible with DE-CP X24-01
- Remote communication for monitoring and maintenance
- Hardware watchdog for digital and analog outputs and for the overall system
- Panel mounting enclosure with IP65 front sealing and IP20 rear sealing
Data recording
- Recording of all process variables
- Integrated recorder functions
- Graphical and numerical data output
- Print functions
- Proof of quality within the framework of DIN ISO 9000
Regulation
- Multi-system control
- All standard control algorithms with parameter switching and setpoint correction
- Special functions (e.g. diffusion processes, F-value calculation)
Control system
- Integrated PLC (S5 © and S7 © compatible)
- Manual operating mode
- Step chain control
- Special functions (e.g. burner all-round control)
Visualization
- System diagram(s) with status display
- Alarm and notification display with help function
- Online process variable display numerically and as trend display
Technical data
Display and operation
- 10.4" TFT with membrane keypad
- Resolution 1024x768 pixels XGA resolution
- LED backlighting
- External USB mouse and/or keyboard can be connected
- Intuitive graphical user interface
Protection class
- Front IP65
- Rear IP20
- Operating ambient temperature 0...+45°C
EMV
- Emission EN 61000-6-4:2007 + A1:2011
- Interference immunity EN 61000-6-2:2005
System
- Intel® Dual Core 2 GHz
- 4GB DDR4 memory
- 40GB M.2 flash memory
- All data including programs, measurements and process status in Flash
- UPS for data integrity
- Multi-stage watchdogs, system status, voltage and temperature monitoring
- Real-time clock RTC, battery-buffered
- Integrated PLC, S5 © and S7 © compatible command set, max. PLC program length: 60,000 commands with time requirement for 1,000 bit commands of < 0.2 ms up to 256 timers, 1024 messages, 1024 alarms (optionally with switch-on delay)
Interfaces DE-CP XX2-01
- 2x Ethernet 2.5GbE with TSN support
- 1 COM DE9 DIN-RS232 (galvanically isolated)
- Further COM DE9 DIN-RS232/RS422/RS485 external Expandable
- 1x USB 3.1 Gen.2 Type C
- 2x USB 3.1 Gen.2 Type A
- 1x USB Demig IO
- Profibus DP (master or slave), RS-485, potential-free, D-Sub socket, 9-pin
- Various protocols integrated: e.g. ModBus TCP and RTU
Power supply DE-CP X4X-01
Main and I/O with separate power supply
- 24V DC ± 15% (Main)
- Power (main) typically 25W, max. 75W when SuperCap UPS is charging
- 24V DC ±15% (I/O)
- Power (I/O) typically 10-20W, max. 50W
- Potential separation GND/PE
- Buffering with SuperCap UPS
Dimensions and weight DE-CP 34X-01
- Aperture size 10" approx. 400x235x4mm
- Cut-out 10" 382x217mm or 284x137mm (adapter frame)
- Installation depth: approx. 235mm (270mm with plug)
- max. wall thickness 6mm
- Weight 10" approx. 6.0 kg
Accessories
- 8 Analog IN card
- 8 Analog OUT card
- 4 Analog IN / 2 Analog OUT Card
- 4 Analog IN/2 Analog OUT (switching output)
- 32 Digital IN card
- 32 Digital OUT card / 32 Digital IN-OUT card
- 24 Digital IN / 16 Digital OUT card
8 Analog IN card
Item number: 601613
8-fold analog input card
- All inputs are galvanically isolated from each other and from the system potential
- DC voltage, DC current measurement possible
- Inputs configurable: 0...100mV 0...500mV
- 0...2V 0...10V
- 0...20mA
- 0...400 Ω (2/3/4-wire technology)
- (error < 0.1% of the measuring range)
- Any combination of input circuitry
- min. Measuring time per channel 20mS
- Double reference junction measurement in the connector plug
Linearization is included in the scope of delivery for the following thermocouples.
- Cu-CuNi Type U ( -200 ... +600 °C)
- Fe-CuNi Type L ( -200 ... +900 °C)
- NiCr-CuNi Type E ( 0 ... +1000 °C)
- Ni-CrNi Type K ( -200 ... +1370 °C)
- PtRh-AuPdPt ( -100 ... +1300 °C)
- PtRh13-Pt Type R ( 0 ... +1740 °C)
- PtRh10-Pt Type S ( 0 ... +1760 °C)
- PtRh30-PtRh6 Type B ( 0 ... +1800 °C)
- WRe3-WRe25 ( 0 ... +2400 °C)
- WRe3-WRe26 ( 0 ... +2500 °C)
- NiCrSi-NiSi Type N ( -270 ... +1400 °C)
- Pt 100 ( -200 ... +800 °C)
8 Analog OUT Card
Item number: 601615
DA 8: 8-fold analog output card
- All outputs are galvanically isolated from the system potential
- Outputs: 0...10V load capacity >= 1kΩ
- 0(4)...20mA Load <= 1000 Ω
- Resolution 12 bit/0.025%
- Output rate dependent on configuration (min. every 100ms)
- Local watchdog function integrated
4 Analog IN / 2 Analog OUT Card
Item number: 601614
AD 4/DA 2: Analog combination card
Analog inputs (4):
- All inputs are galvanically isolated from each other and from the system potential
- DC voltage, DC current measurement possible
- Inputs configurable: 0...100mV 0...500mV
- 0...2V 0...10V
- 0...20mA
- 0...400 Ω (2/3/4-wire technology)
- (error < 0.1% of the measuring range)
- Any combination of input wiring via configuration software
- min. Measuring time per channel 20mS
- Cold junction measurement in the connector plug
Linearization is included in the scope of delivery for the following thermocouples:
- Cu-CuNi Type U ( -200 ... +600 °C)
- Fe-CuNi Type L ( -200 ... +900 °C)
- NiCr-CuNi Type E ( 0 ... +1000 °C)
- Ni-CrNi Type K ( -200 ... +1370 °C)
- PtRh-AuPdPt ( -100 ... +1300 °C)
- PtRh13-Pt Type R ( 0 ... +1740 °C)
- PtRh10-Pt Type S ( 0 ... +1760 °C)
- PtRh30-PtRh6 Type B ( 0 ... +1800 °C)
- WRe3-WRe25 ( 0 ... +2400 °C)
- WRe3-WRe26 ( 0 ... +2500 °C)
- NiCrSi-NiSi Type N ( -270 ... +1400 °C)
- Pt 100 ( -200 ... +800 °C)
Analog outputs (2):
- All outputs are galvanically isolated from the system potential
- Outputs: 0...10V load capacity >=1kΩ
- 0(4)...20mA Load <= 500 Ω
- Resolution 12 bit/ 0.025%
- Output rate dependent on configuration (min. every 100ms)
- Local watchdog function integrated
4 Analog IN / 2 Analog OUT card (switching output)
Item number: 601616
AD 4/DA 2: Analog combination card with limit value switch
Analog inputs (4):
- All inputs are galvanically isolated from each other and from the system potential
- DC voltage, DC current measurement possible
- Inputs configurable: 0...100mV 0...500mV
- 0...2V 0...10V
- 0...20mA
- 0...400 Ω (2/3/4-wire technology)
- (error < 0.1% of the measuring range)
- Any combination of input wiring via configuration software
- min. Measuring time per channel 20mS
- Cold junction measurement in the connector plug
Linearization is included in the scope of delivery for the following thermocouples:
- Cu-CuNi Type U ( -200 ... +600 °C)
Fe-CuNi Type L ( -200 ... +900 °C)
NiCr-CuNi Type E ( 0 ... +1000 °C)
Ni-CrNi Type K ( -200 ... +1370 °C)
PtRh-AuPdPt ( -100 ... +1300 °C)
PtRh13-Pt Type R ( 0 ... +1740 °C)
PtRh10-Pt Type S ( 0 ... +1760 °C)
PtRh30-PtRh6 Type B ( 0 ... +1800 °C)
WRe3-WRe25 ( 0 ... +2400 °C)
WRe3-WRe26 ( 0 ... +2500 °C)
NiCrSi-NiSi Type N ( -270 ... +1400 °C)
Pt 100 ( -200 ... +800 °C)
Analog outputs (2):
- All outputs are galvanically isolated from the system potential
- Outputs: 0...10V load capacity >=1kΩ
- 0(4)...20mA Load <= 500 Ω
- Resolution 12 bit/ 0.025%
- Output rate dependent on configuration (min. every 100ms)
- Local watchdog function integrated
Comparator inputs (2):
- The two inputs 0...10V are at the potential of the analog outputs and are compared internally.
- Potential-free relay output switches depending on the result of the comparator.
32 Digital IN card
Item number: 601611
IN 32: 32-fold digital input card
- All inputs are galvanically isolated from the system potential by optocouplers
- Input potentials 0 V...30V (DC) 15mA; logical 0 < 5V logical 1 > 15V
- Hardware debouncing of all inputs, min. signal length 200ms (other signal lengths possible on request)
32 Digital OUT card / 32 Digital IN-OUT card
Item number: 601612
OUT 32/IO 32: 32-fold digital input/output card
- all outputs can also be configured as inputs
- all outputs and inputs are galvanically isolated from the system potential by optocouplers
- Switching capacity per output max. 30V / max. 0.5A at max. 12W (ohmic load)
- external power supply of the output transistors 24V DC ± 15%
- Local watchdog function integrated
- Input potentials 0 V...30V (DC); logical 0 < 5V logical 1 > 15V
- Hardware debouncing of all inputs, signal length optionally 1.6 ms/0.14ms (longer or shorter signal length possible on request)
24 Digital IN / 16 Digital OUT card
Item number: 601608
IN 24/OUT 16: 24-fold IN/16-fold OUT card
- All inputs are galvanically isolated from the system potential by optocouplers
- Input potentials 0 V...30V (DC) 15mA; logical 0 < 5V logical 1 > 15V
- Hardware debouncing of all inputs, min. signal length 200ms (other signal lengths possible on request)
- All outputs can be loaded with 0.5A (all outputs can be switched on at the same time)
- Short-circuit resistance of all outputs
- Supply voltage 18VDC...36VDC
- Local watchdog function integrated
- Outputs are switched off when the supply voltage is < 16V